On a tenant improvement, most of the HVAC takeoff is ductwork. Each size is measured by the foot and turned into square feet of sheet metal at its gauge, with the wrap or liner, hangers and sealant that go with it. Diffusers, grilles, terminal boxes, fans, fittings and dampers are counts. The air devices carry one more check: their airflow has to add up to what each box delivers, and the takeoff is a good time to find out if it doesn't.
Below is a complete ductwork takeoff in Easy Takeoffs on the mechanical sheet of a small office: rectangular duct with the built-in duct template, round duct with a template of our own, and every device, box and fitting counted. The plan, the takeoff spreadsheet and the marked-up sheet are free to download.

The duct around VAV-1 and VAV-2. Every size is its own group with the gauge in its name, and the diffusers, grilles and boxes are counted in groups of their own.
Open full-size screenshot (opens in a new tab)M1.1 Mechanical Plan
The sample job is Suite 200, the office from the electrical and plumbing pages, and its HVAC is one sheet: M1.1 Mechanical Plan, at 1/4" = 1'-0". The building has a central VAV air handler, and the suite is a shell (note 1). A capped 14" medium pressure stub above the ceiling (keynote 1) feeds five VAV boxes through round duct. Each box feeds rectangular low pressure duct, and round runouts carry the air from it to 19 lay-in diffusers. The return is the ceiling plenum: ten grilles open into it, and the building's existing 24x16 return duct takes the air back (keynote 2). Two ceiling fans exhaust the restrooms.
The notes decide the materials:
- Note 2: medium pressure duct, upstream of the boxes, is round spiral, 2" w.g. pressure class, with every joint sealed.
- Note 3: low pressure duct is rectangular, 1" w.g., 26 gauge where the longer side is 12" or less and 24 gauge from 13" to 30".
- Note 4: each runout is the diffuser's neck size, with a spin-in fitting and a volume damper at the tap. The last 5'-0" may be insulated flex.
- Note 5: all supply duct, medium and low pressure, gets 1-1/2" fiberglass wrap with FSK facing (R-6). The exhaust duct is bare.
- Keynote 3: RT-1 is a 12x10 transfer duct with 1" liner and two elbows, through the full-height conference room wall, for sound.
The schedules give the air devices (two supply diffusers that differ by neck size, and a return grille), the five VAV boxes with their inlet sizes and airflows, and the two exhaust fans. We drew this sheet for practice, so it isn't a real project, but its schedules and notes are written the way an engineer writes them.
- The planM1.1 Mechanical Plan, one ARCH D sheet at 1/4" = 1'-0"PDF, 20 KB
- The takeoffEvery duct run by size and every air device, box and fitting, with the duct materials, as the CSV export wrote itCSV, 17 KB
- The marked-up planM1.1 with every duct run and count on it, then the totals and materialsPDF, 56 KB
Groups by Size, With the Gauge in the Name
Upload the PDF and Easy Takeoffs names the sheet M1.1 Mechanical Plan and suggests its scale, 1/4" = 1'-0", for you to confirm.
The Sheet Metal / Ductwork tool set starts the job with groups for supply, return and exhaust duct, a few common sizes in each with the HVAC Rectangular Duct template already on them, and groups for fittings, air devices and equipment. We changed the sizes to the six on this plan, turned a return size into RT-1, removed the groups this job doesn't use, and added groups for the round duct: the five medium pressure diameters, the 8" and 6" runouts, and the 6" exhaust.
The duct template works in square feet and knows nothing about gauge, so the gauge from note 3 goes into each group's name: 16 x 10 (24 ga) and 14 x 10 (24 ga), and the other four sizes at 26 ga. The name carries into both exports, so nobody has to go back to the notes to order the metal.
Rectangular Duct Into Sheet Metal
Trace each piece of duct along its centerline, from where its size starts to where it changes, into that size's group. Where a trunk steps down from 14 x 10 to 12 x 8, the piece ends at the transition and the next size picks up there. The low pressure supply came to 96'-5" in 14 pieces.
The HVAC Rectangular Duct template figures each group from its width, height and length:
- Sheet metal body is the perimeter times the length, with 15% waste. The 12 x 8 has a perimeter of 40 inches, so its 24'-11" is 83 square feet, 96 with waste.
- Fittings are an allowance, not a count. At the default fitting factor of 1.5, the template adds half the body's metal again: 48 square feet for the 12 x 8.
- Insulation is a choice for each group: none, a 1" internal liner or a 1-1/2" outside wrap. The wrap is figured at its outer face, 1-1/2" out on every side, which for the 12 x 8 is 119 square feet with 10% waste.
- Mastic is a gallon for every 25 feet, rounded up.
- Hangers and rod are a trapeze every 8 feet, with two 3/8" rods of about 2 feet each.

The 12 x 8 group with its six materials. The quantities include each line's waste and round up.
Open full-size screenshot (opens in a new tab)The whole low pressure system, with RT-1:
| Group | Length | Body, sf | Fittings, sf | Wrap, sf | Hangers |
|---|---|---|---|---|---|
| 16 x 10 (24 ga) | 6'-6" | 33 | 17 | 39 | 2 |
| 14 x 10 (24 ga) | 3'-11" | 19 | 10 | 22 | 2 |
| 12 x 8 (26 ga) | 24'-11" | 96 | 48 | 119 | 5 |
| 10 x 8 (26 ga) | 9'-0" | 31 | 16 | 40 | 3 |
| 10 x 6 (26 ga) | 16'-3" | 50 | 25 | 66 | 4 |
| 8 x 6 (26 ga) | 35'-10" | 97 | 49 | 132 | 6 |
| RT-1 12 x 10 (26 ga) | 5'-11" | 25 | 13 | 24 of liner | 2 |
RT-1 uses the same template with the liner in place of the wrap. Its 13 square feet of fitting allowance is what its two elbows will use.
Then sort the metal by gauge. Ductwork is often priced by the pound, and the standard weights for galvanized sheet, 1.156 pounds per square foot at 24 gauge and 0.906 at 26, turn the square feet into pounds. Body and fittings together, the 24 gauge groups come to 79 square feet, about 91 pounds, and the 26 gauge groups with RT-1 to 450 square feet, about 408 pounds. The template stops at square feet; the weight is a line in your spreadsheet, or one you add to your own copy of the template.
Round Duct With a Template of Our Own
There is no built-in template for round duct, and the rectangular one can't be stretched to fit, because it figures the metal from a width and a height. Round duct is bought by the foot by diameter anyway, which makes a round template simple. We made one from the rectangular template with Duplicate & Customize and called it HVAC Round Duct:
- A Duct Diameter replaces the width and height, and we removed the fitting factor and the liner choice.
- Round Duct is the traced length in feet, with 5% waste.
- Duct Wrap Insulation is figured at the wrap's outer face: the circumference of the diameter plus 3", in feet, times the length.
- Mastic and hangers are the same lines as before. We dropped the rod line: small round duct hangs from a strap or a single rod with a band rather than a trapeze, so we price each round hanger complete.

The two lines that make the round template. LF is the traced length; has_wrap is 1 when a group's insulation is the outside wrap.
Open full-size screenshot (opens in a new tab)Applied to the medium pressure mains, the runouts and the exhaust, with the exhaust's insulation set to none:
| Group | Length | Duct, ft | Wrap, sf | Hangers |
|---|---|---|---|---|
| 14" medium pressure | 16'-2" | 17 | 79 | 4 |
| 12" medium pressure | 3'-5" | 4 | 15 | 2 |
| 10" medium pressure | 21'-4" | 23 | 80 | 4 |
| 8" medium pressure | 15'-8" | 17 | 50 | 3 |
| 6" medium pressure | 14'-9" | 16 | 39 | 3 |
| 8" runouts, 7 runs | 28'-5" | 30 | 90 | 9 |
| 6" runouts, 12 runs | 49'-10" | 53 | 130 | 13 |
| 6" exhaust | 6'-9" | 8 | none | 2 |
Hangers on Trunks and Runouts
Hangers are whole pieces, and the right count depends on how the duct runs. A trunk is one continuous line of duct even where its size changes, so its hangers are spaced along the trunk as a whole. The default calculation, Group total, works from each group's combined length, and that suits trunks: the six rectangular sizes, 96 feet of trunk in all, get 16 hangers before waste, about one every 6 feet.
Runouts are separate branches, from 1'-6" to 8'-6" long, and each needs at least one hanger of its own. Figured from the combined length, the twelve 6" runouts, 49'-10" in all, get 7 hangers before waste, fewer than one each. Set the group's Calculation to Per measurement and the template counts whole hangers for each run, then adds them up: 12 before waste, 13 with it. The 8" runouts go from 4 to 8 the same way, because their 8'-6" run needs two.

The 6 inch runouts with Per measurement on: a hanger for each of the twelve runs, plus waste.
Open full-size screenshot (opens in a new tab)Two more things about the template's hangers before they go into the price:
- Rod length. The rod line allows about 2 feet per rod. The architectural sheets put the underside of the deck at 13'-0", 4 feet above the ceiling, so the rods on this job will run closer to 3 feet. Raise the allowance in your own copy of the template, or price the difference.
- Rounding. Each group adds its waste and rounds up on its own, so a group with one hanger lists two. The 64 hangers in the project total are 49 before waste. Mastic adds up the same way: its formula rounds each group up to a whole gallon, so the 15 duct groups list 18 gallons, where the job's 258 feet at 25 feet a gallon is 11.
Air Devices, Boxes and Fittings
The diffusers and grilles are symbols, so symbol search counts them, and this plan has a catch built in. S-1 and S-2 are drawn the same, a square 2 feet on a side with an X through it, except for the neck circle in the middle: 6" for S-1 and 8" for S-2. In Vector mode the search reads the drawing itself, so a box around one S-1 found exactly the 12 S-1 diffusers, and a box around an S-2 found exactly the 7 S-2s. The legend's samples are drawn at half size and matched neither search.

The S-2 search: seven matches, all S-2 diffusers. The note under the results refers to the twelve S-1s.
Open full-size screenshot (opens in a new tab)The S-2 search also says that 12 more places match everything except one mark in the selection, that the mark may be background, and offers to exclude it and search again. Those 12 places are the S-1 diffusers, and the one mark is the neck circle that tells the two types apart. Leave it in. The offer helps when a search box catches a piece of the drawing behind a symbol, not when that piece is the difference between two types.
The R-1 return grille is a square with one diagonal, and every diffuser contains those two marks, so the grille's search matched 29 places: the 10 grilles and all 19 diffusers. Untick the diffusers before adding the counts. Whenever one symbol is drawn inside another, expect the simpler one to match both.
The five VAV boxes, five zone sensors and two exhaust fans are few enough to click with the Count tool. The round fittings and dampers went into one group of their own, with each count named by type:
- 4 tees and 2 elbows on the medium pressure main.
- The manual balancing damper at the building stub (keynote 1).
- A spin-in fitting with a volume damper at each of the 19 runout taps (note 4).
- The tee where the two exhaust fans' ducts meet (keynote 4).
The CSV lists each count with its name, so the types stay apart in the spreadsheet; give each type its own group if you want a subtotal for each. The rectangular fittings stay in the template's allowance. On a job this size you could count them too: the tees and elbows on each trunk and the transitions where a size steps down.
CFM Against the VAV Schedule
Each device tag carries its airflow under the type, and the VAV schedule gives each box's maximum. Add up the devices on each box's duct and the totals should match:
| Box | Serves | Devices on its duct | Device CFM | Schedule max |
|---|---|---|---|---|
| VAV-1 | 101 open office | 8 S-1 at 120 | 960 | 960 |
| VAV-2 | 102 conference | 2 S-2 at 200 | 400 | 400 |
| VAV-3 | 103 and 104 offices | S-2 at 180, S-1 at 120 | 300 | 300 |
| VAV-4 | 105 office, 110 break room | S-2 at 180, 2 S-2 at 160 | 500 | 500 |
| VAV-5 | 100 reception, 108 IT and electrical, 111 corridor | S-2 at 200, S-1 at 120, 2 S-1 at 80 | 480 | 480 |
All five match, 2,640 CFM in all, and every S-1 is at 130 CFM or less and every S-2 between 131 and 240, as the air device schedule requires. On a real set, this check is where a missing diffuser or a wrong tag shows up while it is still a question for the engineer. The boxes themselves are priced from the schedule: one with a 10" inlet, three with 8" and one with 6".
The Duct Material List
| Material | Quantity |
|---|---|
| Galvanized sheet metal, 24 ga, body and fittings | 79 sf, about 91 lb |
| Galvanized sheet metal, 26 ga, body and fittings | 450 sf, about 408 lb |
| Round spiral, medium pressure, 14" | 17 ft |
| Round spiral, medium pressure, 12" | 4 ft |
| Round spiral, medium pressure, 10" | 23 ft |
| Round spiral, medium pressure, 8" | 17 ft |
| Round spiral, medium pressure, 6" | 16 ft |
| Round runouts, 8" and 6" | 30 ft and 53 ft |
| Round exhaust duct, 6" | 8 ft |
| Duct wrap, 1‑1/2" fiberglass with FSK | 901 sf |
| Duct liner, 1" | 24 sf |
| Trapeze hangers, rectangular duct | 24 |
| 3/8" threaded rod | 78 ft |
| Hangers, round duct | 40 |
| Mastic | 18 gal by group, 11 for the job |
The counts go next to it: 12 S-1 and 7 S-2 diffusers, 10 R-1 grilles, 5 VAV boxes, 5 zone sensors, 2 exhaust fans, 19 spin-ins with volume dampers, 4 tees and 2 elbows on the main, the balancing damper and the exhaust tee. That is 258'-6" of duct in 43 pieces and 68 counts.
The CSV ends with a section that adds materials with the same name across groups, so its 168 feet of Round Duct mixes every diameter and its 351 square feet of Sheet Metal Body mixes both gauges. Order from the group lines, as the table does.
Left for the Estimate
A duct takeoff measures what the plan draws. These parts of the bid come from the notes and from your own numbers:
- Flex at the diffusers. Note 4 allows insulated flex for the last 5 feet to each diffuser, and 16 of the 19 runouts are 4 feet or shorter. We measured them all as round duct with wrap. Pricing most of those 78 feet as flex instead is your call, and the spin-ins and dampers stay the same either way.
- The exhaust riser and roof cap. Keynote 4 takes the exhaust up in 8" duct through the roof to roof cap RC-1 with a backdraft damper. The riser is vertical, so there is nothing on the plan to trace; add its height from the ceiling through the roof, and the cap. The curb and the roof patching belong to the landlord's roofer.
- The tie-in. The balancing damper at the stub is counted, but connecting to the capped stub needs a shutdown coordinated with the landlord (keynote 1), which can mean working after hours.
- Sealing at the walls. Note 7 seals every duct penetration of the full-height walls at the conference room and the restrooms.
- Controls, power and heat. The VAV controllers and their tie-in to the building automation system are the controls contractor's (note 9), the fans are wired with the restroom lights (note 11), and heating stays with the existing perimeter system (note 10).
- Testing, adjusting and balancing. An independent agency balances every device to the CFM shown (note 8) and submits its report before the ceilings close (note 12). Carry their price, or confirm the owner hires them.
- Labor and prices. Easy Takeoffs gives you the quantities. Labor units, prices and the bid stay in your estimating program or spreadsheet. If you want a priced fittings database and labor units in one program, a dedicated HVAC estimating system is built for that.
The Ductwork Takeoff Sheet
The CSV export is the ductwork takeoff sheet: every duct piece with its group, page and length, every device, box and fitting, a subtotal for each group, and each duct group's materials before and after waste. The PDF export draws every run and count on M1.1 in its group's color and ends with the totals and materials. Both files from this job are in the downloads above. If your shop prices from a workbook of its own, the Excel export fills in a copy of it: link each group's length, count or material to the cell that prices it, and the formulas and formatting stay yours.
To try it, start a trial and take off the same sheet. Your duct lengths should land within inches of ours; a device count or a CFM total that differs is worth a second look.